Page #5 background image
S8VS
Power ratings 60 W 90 W
Item Type Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance forecast
monitor
Total run time monitor
Efficiency (typical) (rated input voltage) 78% min. 80% min.
Input
Voltage *1 100 to 240 VAC (allowable range 85 to 264 VAC *1)
Frequency *1 50/60 Hz (47 to 450 Hz)
Current
With 100-VAC input 1.7 A max. 2.3 A max.
With 200-VAC input 1.0 A max. 1.4 A max.
Power factor ---
Harmonic current regulation Conforms to EN61000-3-2
Leakage current
With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2
With 100-VAC input 25 A max. (17.5 A max. for BE models)
With 200-VAC input 50 A max. (35 A max. for BE models)
Output
Voltage adjustment range *3 10% to 15% (with V. ADJ) The voltage cannot be adjusted for the S8VS-09024S-@.
Ripple 2.0% (p-p) max. (at rated input/output voltage)
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence (rated input voltage) 1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time *2 1,000 ms max. (at rated input/output voltage)
Hold time *2 20 ms min. (at rated input/output voltage)
Additional
functions
Overload protection *2 105% to 160% of rated load current, inverted L voltage drop, intermittent, automatic reset
Overvoltage protection *2, *4 Yes
Output voltage indication *5 No Yes (selectable) *6 No Yes (selectable) *6
Output current indication *5 No Yes (selectable) *7 No Yes (selectable) *7
Peak-hold current indication *5 No Yes (selectable) *8 No Yes (selectable) *8
Maintenance forecast monitor indication *5 No Yes (selectable) No No Yes (selectable) No
Maintenance forecast monitor output No
Yes (transistor output),
30 VDC max., 50 mA max. *9
No
Total run time monitor indication *5 No Yes (selectable) No Yes (selectable)
Total run time monitor output *5 No
Yes (transistor output),
30 VDC max., 50 mA max. *9
Undervoltage alarm indication *5 No Yes (selectable) No Yes (selectable)
Undervoltage alarm output terminals No Yes (transistor output), 30 VDC max., 50 mA max. *9
Parallel operation No
Series operation Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature
Refer to the derating curve in Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models). (with no icing or
condensation)
Storage temperature 25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA,
detection current for models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance 150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A and based on FCC Class A, Conforms to EN61204-
3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Radiated
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A, Conforms to EN61204-3 EN55011 Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards *11
UL: UL508 (Listing; Class 2 Output: Per UL1310),
UL60950-1
cUL: CSA C22.2 No.107.1 (Class 2 Output: Per
CSA C22.2 No. 223)
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (= VDE0160), EN60950-1
(= VDE0805 Teil 1) *12
KOSHA S Mark *10
UL: UL508 (Listing), UL60950-1
UL for S8VS-09024S-@@@S-@ only: UL508 (Listing, Class 2 Output: Per
UL1310), UL60950-1
cUL: CSA C22.2 No.107.1
cUL for S8VS-09024S-@@@S-@ only: CSA C22.2 No.107.1 (Class 2
Output: Per CSA C22.2 No. 223)
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (= VDE0160),
EN60950-1 (SELV) (= VDE0805 Teil 1) *12
KOSHA S Mark *10
SEMI *11 F47-0706 (With 200-VAC input)
Weight 330 g max. 490 g max.
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in
ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models) on page 24 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. Displayed on 7-segment LED. (character height: 8 mm)
*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.
*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only
*11. DC input is possible only with BE models (allowable range: 80 to 370 VDC). The applicable range for EC Directives and other safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264
VAC).
*12. The standard 60-W, 90-W, 120-W, 180-W, and 240-W models and all 480-W models conform to EN 60950-1.
5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron S8VS Series and is the answer not in the manual?

Omron S8VS Series Specifications

General IconGeneral
Output Power60 W, 120 W, 240 W
MountingDIN Rail Mounting
ProtectionOvercurrent protection, Overvoltage protection
Safety StandardsUL508, EN50178
Dimensions22.5 x 90 x 100 mm
Output Voltage24 VDC