27
Appendix C
Specifications
Item C200H-TS001 C200H-TS002 CS200H-TS101 CS200H-TS102
External input signal (type of
temperature sensing
element).
Thermocouple: K
(CA) or J (IC)
Selectable
Thermocouple: K
(CA) or L (Fe-CuNi)
(DIN) Selectable
Platinum resistance
thermometer bulb:
JPt 100 Ω
Platinum resistance
thermometer bulb: Pt
100 Ω (DIN/ 1989 JIS)
External input points 4 points max. per Unit (1, 2, or 4 points selectable)
Output code to PC 4-digit BCD
Accuracy ± (1% Full scale + 1°C) max. (See note.)
Conversion time 1.2 sec max. per point
Conversion cycle 4.8 sec max. at 4 points per Unit
2.4 sec max. at 2 points per Unit
1.2 sec max. at 1 point per Unit
PC booting time Conversion cycle + 1 PC scan time
Terminal connections Terminal block (removable)
Insulation mode Non-insulated between words. Insulated by photocoupler between input terminal and
PC signals.
Internal power supply 450 mA max. at 5 VDC
External dimensions 35 (W) x 130 (H) x 128 (D)
Weight 400 g max.
Note For example, at a specification of 0° through 400°C, 400°C x 1% + 1°C = ±5°C
max.
Input Specifications
C200H-TS001/002
Temperature Thermocouple
sensing element K (CA): chromel-alumel J (IC):
iron-constant
an/ L
(Fe-CuNi)
Measuring unit
°C °F °C
Measurement
range
1600
1000
800
600
500
400
300
200
150
100
80
50
0
Temperature
specification code
(2-digit BCD)
00 01 02 05 06 07 08 09 10 11 12 13 1403 04