EasyManuals Logo
Home>Panasonic>Air Conditioner>CS-A18BB4P

Panasonic CS-A18BB4P Service Manual

Panasonic CS-A18BB4P
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #133 background imageLoading...
Page #133 background image
position.
(Important notice) / Above procedures are meant for deleting memory on indoor unit’s P.C.
board. And it is not for Address reset.
Indoor unit P.C. board layout
Below drawing shows the location of dip switch 1 (DSW1) on the indoor unit P.C. board.
Dip switch 1 (DSW1). [to be used for manual setting]
26. EMERGENCY OPERATION
Emergency operation
- Emergency operation of outdoor unit / Emergency operation can
be carried out by setting the DSW1 switch on the printed circuit
board of the outdoor unit to the EMERGENCY position. However,
emergency operation is only carried out when an abnormality is
detected by the indoor/outdoor temperature thermistors. / The
resistance values of each thermistor are measured as shown in
the table below to determine if there is an abnormality. / /
Thermistor resistance table
133

Other manuals for Panasonic CS-A18BB4P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A18BB4P and is the answer not in the manual?

Panasonic CS-A18BB4P Specifications

General IconGeneral
BrandPanasonic
ModelCS-A18BB4P
CategoryAir Conditioner
LanguageEnglish

Related product manuals