EasyManuals Logo
Home>Perlick>Refrigerator>HP24Z

Perlick HP24Z Service Manual

Perlick HP24Z
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
Models: HC48RS, RW, WS, WW
Electronic Control: Dixell (XR60CX) -- First Compartment (All models)
Electronic Control: Dixell (XR20CX) -- Second Compartment (RW, WW models)
Defrost Style: Programmed Defrost (12 hours-30 minutes)
Cabinet Lighting: Lights are controlled through a manual on/off switch as well as
through the door switch.
Evaporator Fan: Is controlled by the door switch during Cooling Mode
LOAD COOLING MODE OFF MODE DEFROST MODE
Compressor
Energized
De-Energized De-Energized
Condenser Fan
Energized
De-Energized De-Energized
Evaporator Fan
Energized
De-Energized
Energized
Auxiliary Fan (RS, WS)
Energized
De-Energized De-Energized
Second Compartment Fan
(RW, WW)
Energized
De-Energized
N/A
Models: HP48WO-S, WW-S
Electronic Control: Dixell (XR60CX) -- First Compartment (All models)
Electronic Control: Dixell (XR20CX) -- Second Compartment (WW-S model)
Defrost Style: Programmed Defrost (12 hours-30 minutes)
Cabinet Lighting: Lights are controlled through a manual on/off switch(es) as well as
through the door switch(es).
Evaporator Fan: Is controlled by the door switch during Cooling Mode
LOAD COOLING MODE OFF MODE DEFROST MODE
Compressor
Energized
De-Energized De-Energized
Condenser Fan
Energized
De-Energized De-Energized
Evaporator Fan
Energized
De-Energized
Energized
Auxiliary Fan (RS, WS)
Energized
De-Energized De-Energized
Second Compartment Fan
(RW, WW)
Energized
De-Energized
N/A
Return to Table of Contents
Residential Refrigeration
and Front Venting Commercial Refrigeration
Service Manual
Table 8-18. HC48RS, RW, WS, WW Load Operation Modes
*Auxiliary Fan is used to circulate air through a single zone cabinet.
**Second Compartment Fan is for cooling and is controlled by second compartment controller.
Note: Lights and compartment fans are controlled individually by each door’s switch.
Table 8-19. HP48WO-S, WW-S Load Operation Modes
*Auxiliary Fan is used to circulate air through a single zone cabinet.
**Second Compartment Fan is for cooling and is controlled by second compartment controller.
Note: Lights and compartment fans are controlled individually by each door’s switch.
Electrical System Repair Instructions Page 8-25

Table of Contents

Other manuals for Perlick HP24Z

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Perlick HP24Z and is the answer not in the manual?

Perlick HP24Z Specifications

General IconGeneral
BrandPerlick
ModelHP24Z
CategoryRefrigerator
LanguageEnglish

Related product manuals