QS3.241
Q-Series
24V, 3.4A, SINGLE PHASE INPUT
Jul. 2020 / Rev. 2.3 DS-QS3.241-EN
All parameters are specified at 24V, 3.4A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/26
15. P
ROTECTION
F
EATURES
Output prot
ection Electronically protected against overload, no-load and short-circuits *)
Output over
-voltage protection
typ. 34Vdc
max. 36Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protectio
n IP 20 EN/IEC 60529
Penetration
protection > 3.5mm e.g. screws, small parts
Over
-temperature protection yes Output shut-down with automatic restart
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
T4A H.B.C. not user replaceable
*) In case of a protection event, audible noise may occur.
16. SAFETY FEATURES
Input / output separation
*) SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
Class
of protection I PE (Protective Earth) connection required
Isolation resistance
> 5MOhm input to output, 500Vdc
PE resistance
< 0.1Ohm
Touch current (leakage current)
typ. 0.11mA / 0.26mA 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.15mA / 0.38mA 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.25mA / 0.63mA 230Vac, 50Hz, TN-,TT-mains / IT-mains
< 0.14mA / 0.31mA
110Vac, 50Hz, TN-,TT-mains / IT-mains
< 0.20mA / 0.46mA 132Vac, 60Hz, TN-,TT-mains / IT-mains
< 0.35mA / 0.8mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
17. D
IELECTRIC
S
TRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all input-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1 Dielectric strength
A B C
A
C
N
L
Input
Earth, PE
Output
-
+
B
Type test 60s 2500Vac 3000Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac
Cut-off current setting > 4mA > 4mA > 4mA
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.