QS3.241
Q-Series
24V, 3.4A, SINGLE PHASE INPUT
Jul. 2020 / Rev. 2.3 DS-QS3.241-EN
All parameters are specified at 24V, 3.4A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/26
suitable for TN-, TT- and IT mains networks
85-276Vac continuous operation
60-85Vac full power for 200ms, no damage between 0 and 85Vac
276-300Vac < 500ms
L or N to earth max. 276Vac continuous, IEC 62103
ncy nom. 50–60Hz ±6%
-on voltage typ. 61Vac steady-state value, see Fig. 3-1
-down voltage typ. 58Vac steady-state value, see Fig. 3-1
AC 100V AC 120V AC 230V
typ. 1.67A 1.42A 0.82A at 24V, 3.4A, see Fig. 3-3
actor *) typ. 0.55 0.53 0.47 at 24V, 3.4A, see Fig. 3-4
**) typ. 3.33 3.9 3.88 at 24V, 3.4A
-up delay typ. 360ms 350ms 330ms see Fig. 3-2
0mF, 24V, 3.4A, see Fig. 3-2
typ. 20ms 20ms 22ms 3.4mF, 24V, 3.4A, see Fig. 3-2
-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
60V
300Vac
276V
Shut-down
full
power
for
200ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
0.5 1.51.0 2.0 2.5 3.0 3.5A
0
0.3
0.6
0.9
1.2
1.5
1.8A
Output Current
Input
Current, typ.
230Vac
120Vac
100Vac
Power
Factor, typ.
0.5 1.0 1.5 2.0 3.5A
0.35
0.4
0.45
0.5
0.55
0.6
Output Current
120Vac
230Vac
2.5 3.0
100Vac