Can’t find out failure point or
can’t check. Please contact
with distributor or Pylontech.
Once a certain failure detected following the trouble shooting steps, shut down the battery string
first before replacement to avoid further over discharge to the system due to the self-consumption.
5.2 Replacement of main component
Danger: The Force-H1 is a high voltage DC system, operated by qualified and authorized person
only.
Danger: Before replace the main component must shut off the maintenance battery string’s
power. Must confirm the D+ and D- terminal are without power. The
turn off progress refer to chapter 3.6.5.
5.2.1 Replacement of Battery Module
5.2.1.1 Charge existing module to full (SOC 100%). Make sure new battery
module is 100% as well.
5.2.1.2 Turn off the whole battery string’s power. Must confirm the D+ and D-
terminal are without power. The turn off progress refer to chapter 3.6.5.
5.2.1.3 Dismantle D+ and D- Power Cable, Communication Cable and