26
By RS485: DO NOT need LV-HUB.
1) Make sure all dip switch of master batteries is R000.
R: is the baud rate of RS485, all master batteries shall be the same.
2) Connect communication cable follow the picture:
3) Then turn ON the batteries. After all batteries running and buzzer of master
battery in group1 rings 3 times. Means all groups are online.
For inverter or EMS, The interruption of each RS485 command shall at
least≥1s.
5.10
1) each pair of cable hold max 100A constant current Connect enough pairs of
cable based on calculation of system current.
Multi-group mode
2) For Australian market, an overcurrent and disconnection device that isolates
all live conductors (positive and negative) is required between the battery system
and the inverter
Connect power cable first: