R2K 34 RAIN - RAD - ING - Manuale - 1612.1_firm.L181E
1 Riempimento dell'impianto_MIAH4_R2K_RAIN_PM_EN
1. INSTALLATION
INSTALLER
7. open the air relief valves of the radiators and
check the air removal process. When the
water starts to leak close the radiators air
relief valves.
8. if after performing these operations you
observe a decrease of the water pressure
inside the system, open once again the loading
tap “R” until the pressure gauge indicates the
value of 1.2 bar (fig. 4)
1.1.11. FILLING THE CONDENSATE
COLLECTION SIPHON
Before starting the boiler you have to fill the
condensate collection siphon in order to avoid fuel
reflux through the siphon.
Fill the condensate collection siphon as follows
(see fig. 5):
Unscrew the “T” cap from the siphon, fill three
quarters of the the siphon with water and screw
the “T” cap back in;
Connect the dedicated flexible condensate
draining tube “P” to a waste disposal system.
The condensate can be drained directly in
the sewerage system by inserting an easily
serviceable siphon.
P
T
fig. 4
fig. 5

Other manuals for Radiant R2K 34 RAIN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Radiant R2K 34 RAIN and is the answer not in the manual?

Radiant R2K 34 RAIN Specifications

General IconGeneral
BrandRadiant
ModelR2K 34 RAIN
CategoryBoiler
LanguageEnglish

Related product manuals