53
Diagnostics
DIAGNOSTICS
COOLING MODE
TROUBLESHOOTING TIPS
SYSTEM
PROBLEM
INDICATORS
DISCHARGE
PRESSURE
SUCTION
PRESSURE
SUPERHEAT
Normal:
5°–15°F
[-15° – -9°C]
SUBCOOLING
Normal: See
Charging Chart
COMPRESSOR
AMPS
Overcharge
High High Low High High
Undercharge
Low Low High Low Low
Liquid Restriction
(Drier)
Low Low High High Low
Low Indoor Air ow
Low Low Low Low Low
Dirty Outdoor Coil
High High Low Low High
Low Outdoor
Ambient Temperature
Low Low High High Low
Inef cient
Compressor
Low High High High Low
Indoor TXV Feeler
Bulb Charge Lost
Low Low High High Low
Poorly Insulated
Indoor Sensing Bulb
High High Low Low High
HEATING MODE
TROUBLESHOOTING TIPS
SYSTEM
PROBLEM
INDICATORS
DISCHARGE
PRESSURE
SUCTION
PRESSURE
SUPERHEAT
Normal:
5°–15°F
[-15° – -9°C]
SUBCOOLING
Normal: See
Charging Chart
COMPRESSOR
AMPS
Overcharge
High High OK High High
Undercharge
Low Low OK or High Low Low
Liquid Restriction
(Drier)
Low Low High High Low
Low Outdoor Air ow
Low Low Low Low Low
Dirty Indoor Coil
High High Low Low High
Low Indoor Ambient
Temperature
Low Low OK High Low
Inef cient
Compressor
Low High High High Low
Outdoor TXV Feeler
Bulb Charge Lost
Low Low High High Low
Poorly Insulated
Outdoor Sensing
Bulb
High High Low Low High