Electrical and Physical Data
(-)P16
Factory
Regional
Charge Minimum Standard
Per Circuit Circuit
Statement
Model Number oz. (g) Volts Phase Hertz RLA LRA FLA HP Ampacity MAX MIN High Low Mfr. Part No. Codes
(A) (P) (B) (C) (D) (E) (F) (G) (H) (J) (K) (L) (M) (N) (**)
(S)
RP1624AJ2NA 137 (3884) 208/230 1 60 13.0/13.0 58.3 2.8 1/3 20/20 30/30 25/25 550 (3792) 250 (1723) COPELAND 55-23156-47 9195 None
SP1624AJ2NA
RP1636AJ2NA 156 (4423) 208/230 1 60 17.0/17.0 83 2.8 1/3 25/25 40/40 30/30 550 (3792) 250 (1723) COPELAND 55-23156-36 9196 None
SP1636AJ2NA
RP1648AJ2NA 196 (5557) 208/230 1 60 23.6/23.6 104 1.4 1/4 31/31 50/50 40/40 550 (3792) 250 (1723) COPELAND 55-23156-37 9197 None
SP1648AJ2NA
RP1660AJ2NA 242 (6861) 208/230 1 60 28.8/28.8 152.9 1.4 1/4 38/38 60/60 45/45 550 (3792) 250 (1723) COPELAND 55-23156-34 9198 None
SP1660AJ2NA
Compressor Fan Motor Circuit Breaker Size PSIG (kPa) Compressor
Fuse or HACR Design Pressure