English-13
P037 [Stop Mode] 0/9 0 = “Ramp, CF”
(1)
1 = “Coast, CF”
(1)
2 = “DC Brake, CF”
(1)
3 = “DCBrkAuto,CF”
(1)
4 = “Ramp”
5 = “Coast”
6 = “DC Brake”
7 = “DC BrakeAuto”
8 = “Ramp+EM B,CF”
9 = “Ramp+EM Brk
(1)
Stop input also clears active fault.
0
Active stop mode for all stop sources [e.g. keypad,
run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to
stop input except when P036 [Start Source] is set
for “3-Wire” control. When in three wire control, I/O
Terminal 01 is controlled by P037 [Stop Mode].
P038 [Speed Reference] 0/7 0 = “Drive Pot”
1 = “InternalFreq”
2 = “0-10V Input
3 = “4-20mA Input”
4 = “Preset Freq”
5 = “Comm Port”
6 = “Stp Logic”
7 = “Anlg In Mult”
0
Sets the source of the speed reference to the drive.
Important: When A051 or A052 [Digital Inx Sel] is
set to option 2, 4, 5, 6, 13 or 14 and the digital
input is active, A051, A052, A053 or A054 will
override the speed reference commanded by this
parameter. Refer to Chapter 1 of the PowerFlex 40
User Manual on CD for details.
P039 [Accel Time 1] 0.0/600.0 Secs 0.1 Secs 10.0 Secs
Sets the rate of accel for all speed increases.
P040 [Decel Time 1] 0.1/600.0 Secs 0.1 Secs 10.0 Secs
Sets the rate of decel for all speed decreases.
P041 [Reset To Defalts] 0/1 0 = “Ready/Idle”
1 = “Factory Rset”
0
Resets all parameter values to factory defaults.
P042 [Voltage Class] 2/3
2 = “Low Voltage” (480V)
3 = “High Voltage” (600V)
3
Sets the voltage class of 600V drives.
P043 [Motor OL Ret] 0/1 0 = “Disabled” 1 = “Enabled”
Enables/disables the Motor Overload Retention function.
= Stop drive before changing this parameter.
No. Parameter Min/Max Display/Options Default
Advanced Group Parameters
No. Parameter Min/Max Display/Options Default
A051
A052
A053
A054
[Digital In1 Sel]
I/O Terminal 05
[Digital In2 Sel]
I/O Terminal 06
[Digital In3 Sel]
I/O Terminal 07
[Digital In4 Sel]
I/O Terminal 08
0/27 0 = “Not Used”
1 = “Acc & Dec 2”
2 = “Jog”
3 = “Aux Fault”
4 = “Preset Freq”
5 = “Local”
6 = “Comm Port”
7 = “Clear Fault”
8 = “RampStop,CF”
9 = “CoastStop,CF”
10 = “DCInjStop,CF”
11 = “Jog Forward”
12 = “Jog Reverse”
13 = “10V In Ctrl”
14 = “20mA In Ctrl”
15 = “PID Disable”
16 = “MOP Up”
17 = “MOP Down”
18 = “Timer Start”
19 = “Counter In”
20 = “Reset Timer”
21 = “Reset Countr”
22 = “Rset Tim&Cnt”
23 = “Logic In1”
24 = “Logic In2”
25 = “Current Lmt2”
26 = “Anlg Invert”
27 = “EM Brk Rlse”
4
4
5
11
A055 [Relay Out Sel] 0/22 0 = “Ready/Fault”
1 = “At Frequency”
2 = “MotorRunning”
3 = “Reverse”
4 = “Motor Overld”
5 = “Ramp Reg”
6 = “Above Freq”
7 = “Above Cur”
8 = “Above DCVolt”
9 = “Retries Exst”
10 = “Above Anlg V”
11 = “Logic In 1”
12 = “Logic In 2”
13 = “Logic 1 & 2”
14 = “Logic 1 or 2”
15 = “StpLogic Out”
16 = “Timer Out”
17 = “Counter Out”
18 = “Above PF Ang”
19 = “Anlg In Loss”
20 = “ParamControl”
21 = “NonRec Fault”
22 = “EM Brk Cntrl”
0
A056 [Relay Out Level] 0.0/9999 0.1 0.0
A058
A061
[Opto Out1 Sel]
[Opto Out2 Sel]
0/22 See A055 for Options. 2
1
See the PowerFlex 40 User Manual on CD for more information on parameters.

Other manuals for Rockwell Automation PowerFlex 40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 40 and is the answer not in the manual?

Rockwell Automation PowerFlex 40 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 40
CategoryDC Drives
LanguageEnglish

Related product manuals