English-12
The PowerFlex 40 is designed so that start up is simple and efficient. The Program Group
contains the most commonly used parameters.
Display Group Parameters
No. Parameter Min/Max Display/Options
d001 [Output Freq] 0.0/ [Maximum Freq] 0.1 Hz
d002 [Commanded Freq] 0.0/ [Maximum Freq] 0.1 Hz
d003 [Output Current] 0.00/(Drive Amps × 2) 0.01 Amps
d004 [Output Voltage] 0/Drive Rated Volts 1 VAC
d005 [DC Bus Voltage] Based on Drive Rating 1 VDC
d006 [Drive Status] 0/1 (1 = Condition True) Bit 3
Bit 2 Bit 1 Bit 0
Decelerating Accelerating Forward Running
d007-
d009
[Fault x Code] F2/F122 F1
d010 [Process Display] 0.00/9999 0.01 – 1
d012 [Control Source] 0/9 Digit 1 = Speed Command
Digit 0 = Start Command
(See P038; 9 = “Jog Freq”) (See P036; 9 = “Jog”)
d013 [Contrl In Status] 0/1 (1 = Input Present) Bit 3
Bit 2 Bit 1 Bit 0
DB Trans On Stop Input Dir/REV In Start/FWD In
d014 [Dig In Status] 0/1 (1 = Input Present) Bit 3
Bit 2 Bit 1 Bit 0
Digital In 4 Digital In 3 Digital In 2 Digital In 1
d015 [Comm Status] 0/1 (1 = Condition True) Bit 3
Bit 2 Bit 1 Bit 0
Comm Error DSI Option Transmitting Receiving
d016 [Control SW Ver] 1.00/99.99 0.01
d017 [Drive Type] 1001/9999 1
d018 [Elapsed Run Time] 0/9999 Hrs 1 = 10 Hrs
d019 [Testpoint Data] 0/FFFF 1 Hex
d020 [Analog In 0-10V] 0.0/100.0% 0.1%
d021 [Analog In 4-20mA] 0.0/100.0% 0.1%
d022 [Output Power] 0.00/(Drive Power × 2) 0.01 kW
d023 [Output Powr Fctr] 0.0/180.0 deg 0.1 deg
d024 [Drive Temp] 0/120 degC 1 degC
d025 [Counter Status] 0/9999 1
d026 [Timer Status] 0.0/9999 Secs 0.1 Secs
d028 [Stp Logic Status] 0/7 1
d029 [Torque Current] 0.00/(Drive Amps × 2) 0.01 Amps
Smart Start-Up with Basic Program Group Parameters
= Stop drive before changing this parameter.
No. Parameter Min/Max Display/Options Default
P031 [Motor NP Volts] 20/Drive Rated Volts 1 VAC Based on Drive Rating
Set to the motor nameplate rated volts.
P032 [Motor NP Hertz] 15/400 Hz 1 Hz 60 Hz
Set to the motor nameplate rated frequency.
P033 [Motor OL Current] 0.0/(Drive Rated Amps×2) 0.1 Amps Based on Drive Rating
Set to the maximum allowable motor current.
P034 [Minimum Freq] 0.0/400.0 Hz 0.1 Hz 0.0 Hz
Sets the lowest frequency the drive will output
continuously.
P035 [Maximum Freq] 0/400 Hz 1 Hz 60 Hz
Sets the highest frequency the drive will output.
P036 [Start Source] 0/6 0 = “Keypad”
(1)
1 = “3-Wire”
2 = “2-Wire”
3 = “2-W Lvl Sens”
4 = “2-W Hi Speed”
5 = “Comm Port”
6 = “Momt FWD/REV”
0
Sets the control scheme used to start the drive.
(1)
When active, the Reverse key is also active
unless disabled by A095 [Reverse Disable].
See the PowerFlex 40 User Manual on CD for more information on parameters.

Other manuals for Rockwell Automation PowerFlex 40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 40 and is the answer not in the manual?

Rockwell Automation PowerFlex 40 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 40
CategoryDC Drives
LanguageEnglish

Related product manuals