Chapter 7
Communications
Overview The SMC-Flex provides advanced communications capabilities that
allow it to be started and stopped from multiple sources as well as
provide diagnostic information through the use of communication
interfaces. The SMC-Flex uses the DPI method of communication,
therefore all standard DPI communication interfaces used by other
devices (i.e., PowerFlex Drives) can be used in the SMC-Flex.
ScanPort devices are not supported by the SMC-Flex.
Standard DPI communications cards are available for various
protocols including DeviceNet, ControlNet, Remote I/O, ModBus,
and Profibus® DP. Other modules may be available in the future. For
specific programming examples, configuration, or programming
information, refer to the user manual for the communication interface
being used. A list of available interfaces is located below.
Denotes revision level of user manual. Example: Publication 20COMM-UM002C-EN-P is at
revision C.
Communication Ports The SMC-Flex supports three DPI ports for communication. Ports 2
and 3 are supported through the serial connection on the side of the
device and are typically used to interface with a Human Interface
Module (HIM). Port 2 is the default connection with port 3 available
by installing a splitter on port 2. Port 5 is supported by connecting one
of the communication cards listed above to the internal DPI comm
card connection.
Table 7.A
Protocol Type Cat. No. User Manual
DeviceNet 20-COMM-D 20COMM-UM002-EN-P
ControlNet 20-COMM-C 20COMM-UM003-EN-P
Remote I/O 20-COMM-R 20COMM-UM004-EN-P
Profibus® 20-COMM-P 20COMM-UM006-EN-P
RS-485 20-COMM-S 20COMM-UM005-EN-P
InterBus 20-COMM-I 20COMM-UM007-EN-P
EtherNet/IP 20-COMM-E 20COMM-UM010-EN-P
RS485 HVAC 20-COMM-H 20COMM-UM009-EN-P
ControlNet (Fiber) 20-COMM-Q 20COMM-UM003-EN-P

Table of Contents

Other manuals for Rockwell Automation SMC-Flex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation SMC-Flex and is the answer not in the manual?

Rockwell Automation SMC-Flex Specifications

General IconGeneral
BrandRockwell Automation
ModelSMC-Flex
CategoryTouch terminals
LanguageEnglish

Related product manuals