EasyManuals Logo
Home>RuggedCom>Network Router>RuggedSwitch RSG2100

RuggedCom RuggedSwitch RSG2100 Specification Sheet

RuggedCom RuggedSwitch RSG2100
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
www.RuggedCom.com
5
RuggedSwitch
®
RSG2100
RuggedSwitch
®
RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports
EMI and Environmental Type Tests
Environmental Type Tests
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing), 55°C , 6 cycles
IEC 60255-21-1 Vibration 2g @ (10 - 150) Hz
IEC 60255-21-2 Shock 30g @ 11mS
IEC 61850-3 EMI TYPE TESTS
TEST Description Test Levels Severity Levels
IEC 61000-4-2 ESD
Enclosure Contact +/- 8kV 4
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m Note 1
IEC 61000-4-4 Burst (Fast Transient)
Signal ports +/- 4kV @ 2.5kHz Note 1
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
Earth ground ports +/- 4kV 4
IEC 61000-4-5 Surge
Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
D.C. Power ports +/- 2kV line-to-earth, +/- 1kV line-to-line 3
A.C. Power ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
IEC 61000-4-6 Induced (Conducted) RFI
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
Earth ground ports 10V 3
IEC 61000-4-8 8 Magnetic Field Enclosure ports
40 A/m continuous, 1000 A/m for 1 s Note 1
1000 A/m for 1 s 5
IEC 61000-4-29
Voltage Dips & Interrupts
D.C. Power ports 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A
A.C. Power ports
30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11 100% for 5 periods, 100% for 50 periods N/A
IEC 61000-4-12 Damped Oscillatory
Signal ports 2.5kV common, 1kV diff. mode@1MHz 3
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
IEC 61000-4-16 Mains Frequency Voltage
Signal ports 30V Continuous, 300V for 1s 4
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. Power Supply D.C. Power ports 10% 3
IEC 60255-5 Dielectric Strength
Signal ports 2kVac (Fail-Safe Relay output) N/A
D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A
IEC 60255-5 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
2
Test Description Test Levels
IEEE C37.90.3 ESD
Enclosure Contact +/-2kV, +/-4kV, +/- 8kV
Enclosure Air +/-4kV, +/-8kV, +/-15kV
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m
IEEE C37.90.1 Fast Transient
Signal ports +/- 4kV @ 2.5kHz
D.C. Power ports +/- 4kV
A.C. Power ports +/- 4kV
Earth ground ports3 +/- 4kV
IEEE C37.90.1 Oscillatory
Signal ports 2.5kV common mode @1MHz
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz
IEEE C37.90 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output)
D.C. Power ports 5kV
A.C. Power ports 5kV
IEEE C37.90 Dielectric Strength
Signal ports 2kVac
D.C. Power ports 2kVac
A.C. Power ports 2kVac
Notes: 1. Ruggedcom specified severity levels
2. Meets Class 2 requirements for an all fiber configuration. Class 1 for copper ports.

Other manuals for RuggedCom RuggedSwitch RSG2100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RuggedCom RuggedSwitch RSG2100 and is the answer not in the manual?

RuggedCom RuggedSwitch RSG2100 Specifications

General IconGeneral
BrandRuggedCom
ModelRuggedSwitch RSG2100
CategoryNetwork Router
LanguageEnglish