Hybrid Solar Inverter User Manual
27
28
Prepare the cables according to the below specifications:
Specification
Range
Recommend value
Conductor cross-sectional area of cables (mm²)
4.0 6.0
5.0
External diameter (mm)
4.0 6.0
5.0
The positive cable is connected to the positive port BAT+ of the battery control unit, and the negative
cable is connected to the negative port BAT- of the battery control unit.
Procedure
1. Get the waterproof cover from the accessory bag and cut holes in the rubber plug. Insert the positive
and negative cables through the hole.
2. On both cables, use a 3-mm wide-bladed screwdriver to strip the insulation layer around 8 to 10 mm
length from one cable end.
3. Insert the cable ends to the corresponding sleeves. Use a crimping plier to assembly the cable ends.
4. Insert the assembled cable ends into the blue positive and negative battery connectors. Then, gently pull
the cables backwards to ensure that they are firmly connected.
5. Tighten the nuts on the positive and negative cable connectors.
6. Connect the cables to the BAT+ and BAT- ports on the inverter.
-- End
8 – 10 mm