Page #26 background imageLoading...
Page #26 background image
PDM20 Series
-25-
Function
code
Description Set range Unit Default
Display
level
Modific
ationlev
el
Notes
P0.28
Current
percentage of
water shortage
protection
detection
0.0
100.0
% 40.0 1
It is valid only when
P0.25=01.
Percentage of motor
rated current. When
running current is
smaller than this
current, it judges as
water shortage.
P0.29
Water
shortage
protection
detection time
0900.0 s 20.0
P0.30
Self-restarting
delay of water
shortage
protection
09999 min 15 1
If it is set to be 0, use
pressure to self-reset
water shortage.
P0.31 Self-sleep rate 130 3 1
Increase this value
when the system can’t
sleep.
P0.32
Inflow
detection
pressure
0.0
P0.00
bar 1.0 1
After inflow pressure is
larger than detection
pressure time
(P0.33),water shortage
fault is automatically
reset.
P0.33
Inflow
detection time
0.0
100.0
s1.0 1
P0.34
Lower limit of
AI
0.0
P0.35
V/mA 4.00
P0.35
Upper limit of
AI
P0.34
20.00
V/mA 20.00
P0.36
Acceleration
time
0.1
3600
s5.0
P0.37
Deceleration
time
0.1
3600
s3.0