R6 Series
- 19 -
R6-20K-T3-32-LV, R6-25K/30K-T4-32-LV
Model
R6-20K-T3-32-LV
R6-25K-T4-32-LV
R6-30K-T4-32-LV
Input (DC)
Max. PV Array Power [Wp]@STC
30000
37500
45000
Max. Input Voltage [V]
1100
MPP Voltage Range [V]
180-1000
Nominal Input Voltage [V]
600
Startup Voltage [V]
200
Max. Input Current [A]
32/32/32
32/32/32/32
Number of MPP Trackers
3
4
Number of Strings per MPP Tracker
2/2/2
2/2/2/2
Output (AC)
Rated AC Output Power [W]
20000
25000
30000
Max. Apparent Power [VA] *
1
22000
27500
30000
Rated ACOutput Current [A]@230Vac
52.5
65.6
78.7
Max. AC Output Current [A]
57.7
72.2
78.7
Nominal AC Voltage/ Range [V]
127V(F-N)/220V(F-F); 101.6-139.7(F-N)
Nominal ACGrid Frequency/ Range [Hz]
50, 60 / 44-55, 54-65
Total Distortion Harmonic [THD]
<3%
Power Factor
0.8 leading0.8 lagging
Feed-in Phase/AC Connection Phases
3/3
Efficiency
Max. Efficiency
98.8%
Euro Efficiency
98.5%
Protection
DCI Monitoring
Integrated
GFCI Monitoring
Integrated
Grid Monitoring
Integrated
AC Grounding Detection
Integrated
AC Short-Circuit Protection
Integrated
DC Insulation Resistance Detection
Integrated
DC Surge Protection
Type II
AC Surge Protection
Type III
Anti-islanding Protection
AFD