Page #106 background imageLoading...
Page #106 background image
21
7. Remote Control Unit Installation Position
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do
not install the remote control unit in the following places:
G In direct sunlight
G Behind a curtain or other place where it is covered
G More than 26' (8 m) away from the air conditioner
G In the path of the air conditioner’s airstream
G Where it may become extremely hot or cold
G Where it may be subject to electrical or magnetic
interference
G Where there is an obstacle between the remote con-
trol unit and the air conditioner (since a check signal
is sent from the remote control unit every 5 minutes)
7-1. Mounting on a Wall
Before mounting the remote control unit, press the
ON/OFF operation button at the mounting location to
make sure that the air conditioner operates from that
location. The indoor unit should make a beeping sound
to indicate that it has received the signal.
Fig. 36
To take out the remote control unit, pull it forward.
I Service Valve Connections
a) Temporary connection:
Screw in 3 – 5 turns by hand. (Fig. 34)
b) To fasten the flare nuts, apply specified torque
as Table 8 and Fig. 35.
Table 8
Fig. 34
Fig. 35
CAUTION
Be sure to tighten the flare nut
using the prescribed torque. If the
nut is over-tightened, refrigerant
leakage may occur.
Torque wrench
Press
Set in
place
Remote control
unit mount
Mounting screws
Rear side
Hole
To prevent loss of the remote control
unit, you can connect the remote
control unit to the mount by passing
a string through the remote control
unit and attachment hole.
5/32 5/8" (4 16 mm)
(included)
Tube Dia. Tightening Torque
1/4" (6.35 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)
3/8" (9.52 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)
1/2" (12.70 mm) Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)
5/8" (15.88 mm) Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)
08-193 XHS1271 9/12/08 2:58 PM Page 21

Table of Contents

Other manuals for Sanyo CH1872

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo CH1872 and is the answer not in the manual?

Sanyo CH1872 Specifications

General IconGeneral
BrandSanyo
ModelCH1872
CategoryAir Conditioner
LanguageEnglish

Related product manuals