Page #50 background image
Outdoor Unit : CM1972A
Indoor Unit : XMS1272 × 3
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
NOTE
RATING CAPACITY: 18,300 BTU/h AIR FLOW RATE: 706 CFM
ROODTUOROODNI
ENT. TEMP.
o
F (
o
.PMET TNEIBMA)C
o
F (
o
C)
W.B. D.B. 65 75 85 95 105115
(18.3)(23.9)(29.4) (35.0) (40.6)(46.1)
TC 18,380 17,78017,130 16,61015,83014,990
CI
0.86 1.06 1.26 1.40 1.61 1.81
72 (22.2) SHC 15,860 15,590 15,310 15,040 14,77014,350
59 76 (24.4) SHC 18,380 17,78017,130 16,610 15,83014,990
(15.0) 80 (26.7) SHC 18,380 17,78017,130 16,610 15,83014,990
84 (28.9) SHC 18,380 17,780 17,130 16,610 15,83014,990
88 (31.1) SHC 18,380 17,780 17,130 16,610 15,83014,990
TC 19,230 18,62017,950 17,450 16,64015,780
CI 0.86 1.07 1.28 1.42 1.63 1.85
72 (22.2) SHC 12,980 12,710 12,430 12,16011,890 11,470
63 76 (24.4) SHC 15,590 15,31015,040 14,770 14,49014,080
(17.2) 80 (26.7) SHC 18,330 18,06017,780 17,450 16,64015,780
84 (28.9) SHC 19,230 18,620 17,950 17,450 16,64015,780
88 (31.1) SHC 19,230 18,620 17,950 17,450 16,64015,780
TC 20,090 19,46018,780 #18,30017,480 16,580
CI
0.86 1.08 1.29 1.44 1.66 1.88
72 (22.2) SHC 9,970 9,8309,550 9,280 9,000 8,730
67 76 (24.4) SHC 12,570 12,43012,160 11,890 11,610 11,340
(19.4) 80 (26.7) SHC 15,310 15,04014,900 14,630 14,35014,080
84 (28.9) SHC 17,920 17,650 17,510 17,230 16,96016,580
88 (31.1) SHC 20,090 19,460 18,780 18,300 17,48016,580
TC 20,930 20,30019,610 19,160 18,32017,100
CI
0.86 1.09 1.31 1.45 1.69 1.89
72 (22.2) SHC 6,950 6,6706,400 6,260 5,990 5,580
71 76 (24.4) SHC 9,5509,280 9,0008,870 8,5908,180
(21.7) 80 (26.7) SHC 12,300 12,02011,750 11,610 11,340 10,930
84 (28.9) SHC 14,900 14,630 14,350 14,220 13,94013,530
88 (31.1) SHC 17,510 17,230 16,960 16,820 16,55016,140
TC 21,660 21,03020,330 19,930 19,08017,510
CI
0.87 1.10 1.34 1.47 1.72 1.89
75 76 (24.4) SHC 6,5406,260 6,1205,990 5,7105,300
(23.9) 80 (26.7) SHC 9,2809,000 8,8708,730 8,4608,040
84 (28.9) SHC 11,89011,61011,47011,340 11,060 10,510
88 (31.1) SHC 14,490 14,220 14,080 13,940 13,67013,120