9/13
Building Technologies Division CC1N7130en
Infrastructure & Cities Sector 22.08.2013
Operation, display, diagnostics
Lockout reset button «EK» is the key operating element for resetting
the burner control and for activating / deactivating the diagnostic
LED
7130z06e/0700
Red
Yellow
Green
The multicolor signal lamp (LED) in the lockout reset button is the key
indicating element for both visual diagnostics and interface diagnostics.
Both «EK» and LED are located under the transparent cover of the lockout reset
button.
There are 2 diagnostic choices:
1. Visual diagnostics: Operational status indication or diagnostics of the cause of
fault.
2. Interface diagnostics: With the help of the interface OCI400 and PC software
ACS400 / ACS410 or flue gas analyzers of different makes.
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color
codes according to the color code table given below.
During startup, status indication takes place according to the following table:
Color code table for multicolor signal lamp (LED)
Waiting time «tw», other waiting states
........................................
........................................
Ignition phase, ignition controlled
........................................
Operation, flame not o.k.
Extraneous light on burner startup
.......................................
Error code output (refer to «Error code
S S S S
S
Flashing red