7 / 13
Siemens Room temperature controller REV17.. CE1N2203en
Building Technologies 24.04.2008
Technical features
DIP switches
ON / OFF 1 2 3 4 5 6 7
Sensor calibration On
Periodic pump run
and anti-lime function
On
A
Sensor calibration Off
Periodic pump run
and anti-lime function
Off
E
Setpoint limitation 16…35 °C
Quartz
B
Setpoint limitation 3…35 °C
Radio clock
F
Temperature display °F
C
Temperature display °C
PID self-learning
PID 6
PID12
D
2-point
After you change one or several
DIP switch positions, you must
press the DIP switch reset button
to reset the DIP switch.
Otherwise, the previous setting
remains active!
DIP switch reset
ON
1 342
2211Z32
567 89
G
Factory setting: All DIP switches to OFF
If the displayed room temperature does not match the measured room temperature, the
temperature sensor can be recalibrated.
Set DIP switch to ON and press the DIP switch reset button:
CAL symbol is displayed. The currently measured temperature flashes.
Press
or to recalibrate by max. ± 5 °C.
Set DIP switch to OFF and press the DIP switch reset button to save the settings.
The minimum setpoint limitation of 16 °C prevents undesired heat transfer to neighboring
spaces in buildings featuring several heating zones.
DIP switch ON: Setpoint limitation 16…35 °C.
DIP switch OFF: Setpoint limitation 3…35 °C (factory setting).
Press the DIP switch reset button to save the settings.
DIP switch ON: Temperature display in °F.
DIP switch OFF: Temperature display in °C (factory setting).
Press the DIP switch reset button to save the settings.
A Sensor calibration:
DIP switch 1
B Setpoint limitation:
DIP switch 2
C Temperature display in
°C or °F:
DIP switch 3