12.98 Forming
Siemens AG 6SE7087-7NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 6-1
6 Forming
If a unit has been non-operational for more than one year, the DC link
capacitors have to be newly formed. If this is not carried out, the unit
can be damaged when the line voltage is powered up.
If the unit was started-up within one year after having been
manufactured, the DC link capacitors do not have to be re-formed. The
date of manufacture of the unit can be read from the serial number.
(Example: RFU-J60147512345)
Position Example Meaning
1 to 3 RFU- Place of manufacture
4J
K
L
M
1997
1998
1999
2000
5 1 to 9
O
N
D
January to September
October
November
December
6 to 15 Not relevant for forming
The following applies for the above example:
Manufacture took place in June 1997.
During forming, the DC link of the unit is connected up via a rectifier, a
smoothing capacitor and a resistor.
As a result, the DC link capacitors receive a defined voltage and a
limited current, and the internal conditions necessary for the function of
the DC link capacitors are restored.
C / L+
D / L-
PE3
AC
R
3 AC 400 V
Forming
DC link
fuse
DC link
Fig. 6-1 Forming circuit
How the serial
number is made up
www . ElectricalPartManuals . com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOVERT MASTERDRIVES 6SE70 P Series and is the answer not in the manual?

Siemens SIMOVERT MASTERDRIVES 6SE70 P Series Specifications

General IconGeneral
BrandSiemens
ModelSIMOVERT MASTERDRIVES 6SE70 P Series
CategoryMedia Converter
LanguageEnglish

Related product manuals