Operating
6.4 20 mA calibration
SITRANS LU150
Operating Instructions, 03/2016, A5E34590123-AB
27
20 mA calibration initiated
view stored 20 mA calibration value
to increase to new calibration value
Blanking is used to ignore the zone in front of the transducer where false echoes are at a level
that interfere with the processing of the true echo. It is measured outward from the sensor face.
The minimum recommended blanking value is 0.25 m (0.82 ft) but can be increased in order to
extend the blanking.