Page #50 background image
50
TUTORBIT
COSMOGAS
4 - INSTALLATION
4.21.11 - 1 heating zones, DHW, DHW return, solar, 2 tanks (1 for solar and 1 for boiler) and solar transfer function
Figure 4-33 - Hydraulic connection
Settings:
Conguration > System >
Number of Modules 1
Module 1 Heating
Outdoor sensor No
DHW Yes
DHW return sensor Yes
DHW Mode Sensor
Unit of measure °C
Number of Zones 1
Antilegionella Yes
Shu󰀪e type pump Antilegionella
Solar Yes
Solar Atistagnation Yes
Solar Antifrost Yes
Modbus enable No
Heat pump No
Conguration > Zones > 3 way valve > 3 way valve 1> Zone type Mix
NOTE: The mixing pump (53) must be set as “Anti-legionella”.
NOTE: The mixing pump (53) also acts as a transfer by means of relay R1.