E
With feet and no rack mounting brackets
F
With fl ow switch
P
High pressure pump mounted
Rc
N
NPT thread
A
Air-cooled
2
200 to 240 V AC HECR010
5
100 to 240 V AC HECR002, 004, 006, 008
002
200 W
004
400 W
006
510 W
008
800 W
010
1 kW
5A
Cooling capacity
Radiating method
Power supply
Option
Pipe thread
How to Order
Specifi cations
Model HECR002-A HECR004-A HECR006-A HECR008-A HECR010-A
Cooling method Thermoelectric device (Thermo-module)
Radiating method Forced air cooling
Control method Cooling/Heating automatic shift PID control
Ambient temperature/humidity 10 to 35 °C, 35 to 80 % RH (No condensation)
Circulating fl uid system
Circulating fl uid Tap water, Ethylene glycol 20 %
Set temperature range 10.0 to 60.0 °C (No condensation)
Cooling capacity
200 W (Tap water)
Note 1)
400 W (Tap water)
Note 1)
510 W (Tap water)
Note 1)
800 W (Tap water)
Note 2)
1 kW (Tap water)
Note 2)
Heating capacity
600 W (Tap water)
Note 1)
1 kW (Tap water)
Note 1)
1.2 kW (Tap water)
Note 1)
1.4 kW (Tap water)
Note 2)
2 kW (Tap water)
Note 2)
Temperature stability
Note 3)
±0.01 to 0.03 °C
Pump capacity Refer to the performance charts. (Page 12)
Tank capacity Approx. 1.3 L
Port size Rc 1/4 Rc 3/8
Fluid contact material
Stainless steel, EPDM, NBR, Ceramics,
PPE, Carbon, PP, PE, PPS (High pressure)
Stainless steel, EPDM, NBR, Ceramics, PPE, PPS, Carbon, PP, PE, Nylon,
POM (HECR008, 010), PVC (High pressure)
Electrical system
Power supply Single-phase 100 to 240 V AC ±10 %, 50/60 Hz
Single-phase 200 to 240
V AC ±10 %, 50/60 Hz
Overcurrent protector 10 A 14 A
Current consumption
5 A (100 V) to 2.5 A (240 V)
9 A (100 V) to 4 A (240 V)
10 A (100 V) to 4 A (240 V)
8 A (200 V)
Power consumption 440 W
Note 1)
850 W
Note 1)
900 W
Note 2)
1500 W
Note 2)
Alarm Refer to “Alarm.” (Page 18)
Communications RS232C/RS-485
Weight Approx. 14 kg Approx. 18 kg Approx. 21 kg Approx. 31 kg Approx. 33 kg
Accessories
Power supply connector, Operation Manual
Power supply cable should be ordered as an option (sold separately) or prepared by the user.
Safety standards CE marking, UL (NRTL) standards
Note 1) Conditions: Set temperature 25 °C, Ambient temperature 25 °C, Circulating fl ow rate 3 l/min
Note 2) Conditions: Set temperature 25 °C, Ambient temperature 25 °C, Circulating fl ow rate 4 l/min
Note 3) The indicated values are with a stable load without turbulence in the operating conditions. It may be out of this range in some other operating
conditions.
¡ When multiple options are combined, indicate
symbols in alphabetical order.
Air-cooled
HECR 002
Thermo-con/
Rack Mount Type
Series HECR
(UL Standards)
7

Other manuals for SMC Networks HECR Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HECR Series and is the answer not in the manual?

SMC Networks HECR Series Specifications

General IconGeneral
BrandSMC Networks
ModelHECR Series
CategoryChiller
LanguageEnglish

Related product manuals