SE2200 SE3000 SE3500 SE4000
SE4000-
16A
SE5000 SE6000 Unit
Overvoltage category III
Input
Maximum DC power
(Module STC)
2950 4050 4700 5400 5000 6750 8100 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
500 Vdc
Nominal DC input
voltage
350 Vdc
Maximum input
current
8.5 11.5 13.5 15.5 15.5 19.5 23 Adc
Maximum back-feed
current
0 Adc
Reverse-polarity
protection
Yes
Ground-fault
isolation detection
600 kΩ Sensitivity
Overvoltage category II
Maximum inverter
efficiency
97.6 %
European weighted
efficiency
97.6 97.6 97.5 97.5 97.5 97.4 97.4 %
Night-time power
consumption
< 2.5 W
Additional Features
Supported
communication
interfaces
(1)
RS485, RS232, Ethernet, ZigBee (optional), Built-in GSM
(optional)
Smart Energy
Management
Export Limitation, StorEdge applications
Standard Compliance
Safety IEC-62103 (EN50178), IEC-62109
Grid connection
standards
VDE-AR-N-4105, VDE 0126-1-1, AS-4777, RD-1663, DK 5940
(1)
Refer to Datasheets -> Communications category in Downloads page for specifications of optional communication
options: http://www.solaredge.com/groups/support/downloads
Technical Specifications - Single Phase Inverters (Europe &APAC) 103