Location
Indoor
Installation
Outdoor Installation
Locations where the
annual average high
temperature
(1)
is below
25˚C / 77˚F
20 cm / 8"
between
inverters
5 cm / 2" between inverters (if
inverters are also installed one
above the other, maintain the
indoor installation clearance)
Locations where the
annual average high
temperature
1
is above
25˚C / 77˚F
40 cm / 16"
between
inverters
Figure 9: Clearance
(1)
Annual average high temperature – the average of the 12 monthly average highs, for
example:
Refer to http://www.weatherbase.com/ to find the value in your location.
-Three Phase System Installation Guide MAN-01-00057-4.1
28 Mounting the Inverter