| Installation
7.7.1 Sylodyn vibration kit (if used)
The responsibility for the Sylodyn vibration kit installation is with the buyer/installer.
Important
Risk of damage to the fan due to incorrect installed vibration dampers
♦ The fan shall rest entirely on the sylodyn anti vibration blocks. It is important that the fan is not pressed
against the mounting frame, therefore the minimum distance of 15 mm has to be kept, see following
picture.
1
Hexagonal head set screw
2
Sylodyn anti
vibration block
Available as Systemair accessory with a hole Ø
16mm
3
Safety plate Available as Systemair accessory with a hole Ø
16mm
4
Hexagonal nut
5
Mounting foot
6
Mounting frame
7.8 Lifting and positioning
The weight of the fan units varies depending on the motor size and accessories. As a result, the fan unit can also be
very bulky and heavy. You can find precise information on the name plate or the data sheet.
Caution
Risk of parts falling down
♦ When fitting the fan, pay attention to its weight and the weight of the components.
Lifting
♦ Lift the fan unit slowly and carefully.
♦ Use hoisting gear permitted for the weight of the fan.
♦ Attach the hoisting equipment to flanges and foot
bores or at the marked places.
♦ Use transport equipment (e.g. lifting eyes) if available.
♦ Please observe the marking “oben/top” on the fan.
Positioning
♦ Observe the arrows on the name plate or the housing
of the fan. They show the direction of rotation and air
flow.
♦ Position the fan unit so that it is standing in the
planned direction of flow.
♦ Provide enough free space for inspection and
maintenance work on the fan unit.
Anchor
♦ Use suitable fittings.
♦ Screw the fittings with the correct tightening torques, see Table 14 Tightening torques according to DIN 13, page
15
♦ If you are not sure, contact Systemair.
7.9 Installation axial fans/AXCBF
Installation is possible in any mounting position. From size 1250 and above, please contact Systemair if the mounting
position should be different to horizontal or vertical.
| 004