4
|
Description
5.1.1 Technical data of the fan
The technical data of the fan can be seen on the name plate or the data sheet.
5.1.2 Motor data
The motor data can be found on the name plate of the motor or in the technical documents of the motor manufacturer.
5.1.3 Temperature types
Table 2 Types of fans
Type
Diameter
[mm]
Long-term operation
–20°C...55°C
(K) 250°C/
120 min.
(B) 300°C/
120 min.
(F) 400°C/
120 min.
AXC/AXR/AXS/
AXCP/AXCPV
315 — 1600 X
AXC...(K)/AXR...
(K)
315 — 1600 X X
AXC...(B)/AXR...
(B)/AXCP...(B)/
AXCPV...(B)
315 — 1600 X X
AXC...(F)AXR...(F)
315 — 1600 X X
AJR/AJ8
315 — 400 X
AJR...(K)/AJ8...(K)
315 — 400 X X
AJR...(B)AJ8...
(B)/
315 — 400 X X
AJR...(F)/AJ8...(F)
315 — 400 X X
IV
50, 85, 100
X
IV...(B) 50, 85, 100
X X
IV...(F) 50, 85, 100
X X
AXCBF- Thermo fans are equipped with an encapsulated motor, permanent operation temperature up to 200°C.
5.2 Description axial fans (AXC, AXR, AXS, AXCP, AXCPV)
• In B3 conventional motors, the motor bracket is made from galvanized steel sheet. B30 “pad mounted” motors are
fitted in the housing via threaded rods or a welded motor support.
• The motor with impeller is mounted to a sturdy supporting structure made of galvanized steel sheet.
| 004