4
| Technical Data
The unit weight is 77 kg.
3.2 Duct connections
Fig. 4 Duct connections
Symbol
Description
Symbol
Description
Supply air
Outdoor air
Exhaust air
Extract air
3.3 Installation recommendation regarding condensation
3.3.1 Condensation inside of the unit
The unit should run continuously. If the unit is intended to be stopped by the user manually or due to calendar function
we recommend to install air tight dampers at extract and supply air ducts. The dampers will ensure that no air circulates
from the warm parts of the building through the unit to outside (chimney effect). If no dampers are installed there is risk
of condensation inside the unit and the outdoor ducts during these stop periods. It also might be that cold air from out-
side could pass the unit and enter into the building. That could cause condensation outside the supply and extract air
ducts and even at the valves in the rooms.
When the unit is not running due to late commissioning in winter time, the supply and extract air ducts should be dis-
connected and closed due to above mentioned effects until commissioning and regular operation.
3.3.2 Condensation outside of the unit
1. Room temperature 26°C
2. Room temperature 24°C
3. Room temperature 22°C
4. Room temperature 20°C
When the unit is installed in warm humid areas (like laun-
dry) together with low outdoor temperature there is a
certain point where moisture can condense outside of the
casing. The condensation relation to indoor relative hu-
midity, room and outdoor temperature is shown diagram
below. The condensation outside of the unit do not occur
in zones bellow each curve.
Important
Recommendation: If condensation occurs,
increase ventilation in area close to the unit.
Examples when condensation outside of the unit can
occur:
Example A: If the unit is installed in room where tempera-
ture is 24°C, outside temperature is –15°C, then dew will
start accumulating when relative humidity is 46% and
higher.
333547 | v1.1

Other manuals for SystemAir SAVE VSR 500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir SAVE VSR 500 and is the answer not in the manual?

SystemAir SAVE VSR 500 Specifications

General IconGeneral
BrandSystemAir
ModelSAVE VSR 500
CategoryFan
LanguageEnglish

Related product manuals