2.3DescriptionofInternalcomponents
2.3.1SupplyandExtractairFans
ThefanshaveexternalrotormotorsofECtypewhichcanbesteplesslycontrolledindividually0–100%.It
ispossibletoprogramthespeedin2steps(normal/reduced)dependingontheprogrammingoftheweek
schedule.Themotorbearingsarelifetimelubricatedandmaintenancefree.Itispossibletoremovethe
fansforcleaning,seechapter5formoreinformation.
2.3.1.1PressuretransmitterFans
2pressuretransmittersmaintaintheairowataconstantlevelbymeasuringthedifferentialpressureover
theinletconeofthefanimpellers(pos.9gure1,pos.10gure2).Thepressuretransmittersareinstalled
fromfactoryinallunitswithCAVcontrol.InVAVunitsthepressuretransmitterswillnotbemountedin
theunitfromfactory.Insteadtheywillbedeliveredlooselywiththeunittobemountedinthesupplyand
extractairducts,see“Installationinstructions”formoreinformationconcerningVAVinstalltions.
2.3.2SupplyandExtractairFilters
TheltersareofbagltertypewithlterqualityF7forthesupplyairlterandF5fortheextractairlter.
Theltersneedtobereplacedwhenpolluted.Newsetsoflterscanbeacquiredfromyourinstalleror
wholesaler.
2.3.2.1Pressureguardlters
Apressureguardmeasuresthedifferentialpressureoverthesupplyandextractairlters(pos.10gure
1,pos.9gure2).Whenthepressuredropreachesthesetvalueanalarmistriggeredinthemain
regulator.Thedifferentialpressurecanbesetbetween40and300Pa.Thepressureswitchispreset
fromfactoryto240Pa.
2.3.3HeatExchanger
TopvexSR/TRmodelsareequippedwithahighlyefcient,beltdriven,rotatingheatexchanger.Required
supplyairtemperatureisthereforenormallymaintainedwithoutaddingadditionalheat.Theoperationof
theheatexchangerisautomaticanddependsonthesettemperature.Anextradrivingbeltisincludedon
therotorondelivery(pos.8gure1andgure2).
Theheatexchangerisremovableforcleaningandmaintenance,seechapter5formoreinformation.
2.3.3.1Rotormotor
Therotormotordrivestheexchangerrotorwithavariablerpmaslongasthereisaheatdemand.The
motoriscontrolledbyananalogue0-10Vcontrolsignalgure1andgure2).
2.3.3.2Rotationguard
Asensorregisterstherotationoftheheatexchangerrotor.It’sconnectedtothemainregulatorwhich
givesanalarmiftherotorstopswhilethereisaheatdemand(pos.7gure1andgure2).
2.3.4Temperaturesensors
4temperaturesensors(PT1000)areincludedintheunitfromfactory:
Supplyairsensor
Extractairsensor
Outdoorairsensor
Exhaustairsensor
TopvexSR/TR03,SR/TR04,SR/TR06OperationandMaintenanceInstructions
206902
4
SystemairAB

Other manuals for SystemAir Topvex SR04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SR04 and is the answer not in the manual?

SystemAir Topvex SR04 Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SR04
CategoryAir Handlers
LanguageEnglish

Related product manuals