10
|
Commissioning
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
→Alarm events
Alarm log list along with the time
and date they occurred.
Move down and up in the list by
pressing ↑↓.
→Input/Output
→AI
Status of the Analogue inputs.
→AI exp3
Status of the Analogue inputs for
expansion unit.
Only visible for counter-/crossflow
units with a connected pressure
module
→AI exp4
→DI
Status of the Digital inputs.
→UI
Status of Universal Analogue inputs
or Universal Digital inputs.
→UI exp3
Status of the Universal Analogue
inputs for expansion unit.
Only visible for counter-/crossflow
units with a connected pressure
module
→UI exp4
→AO
Status of the Analogue outputs.
→DO
Status of the Digital outputs.
→Temperature
Extract air temp
Actual: ºC
Setp: 22.0ºC→↓
Configured temperature control
(default is Extract air temp).
Actual temperature in the chosen
control mode.
Set-point temperature for the
chosen control mode.
If cascade control
Max/min supply
setp.
Max: 30ºC
Min: 14.0ºC
Set the maximum and minimum
allowed supply air temperature in
case of cascade control.
Logon to service level needed to
change settings.
Outdoor temp: ºC
Supply air temp
Act.: ºC
Setp: 18ºC→↓
Neutral zone 0.0 °C
Actual outdoor air temperature.
Actual supply air temperature.
Calculated supply air set point. The
extract air controller output signal
generates the supply air
controller’s set point value.
A neutral zone can be set around
the setpoint value.
Note:
See Corrigo manual-
Ventilation application for
more information.
Frost protection
Actual: ºC↓
Actual water temperature in the
water heating battery. (Only visible
for HW units).