Start-up
5.3 Checking the operation
Check the following:
Q
The temperature of the water entering the evapo-
rator.
Q
The temperature of the water leaving the evapora-
tor.
Q
The level of the water flow rate in the evaporator,
if possible.
Q
The current absorption upon the start of the com-
pressor and in case of stabilised operation.
Q
The fan’s current absorption.
Check that the condensing and evaporation tempe-
ratures, during operation at high and low pressure
detected by the pressure gauges of the refrigerant,
are within the following range:
(On the units not provided with HP/LP pressure gau-
ges for the refrigerant, connect a pressure gauge to
the Shrader valves on the refrigeration circuit).
5.4 Delivery to the customer
Q
Train the user according to the instructions provi-
ded in Section 6.
HP side
Approx. 15 to 21°C above the
temperature of the air entering the
condenser, for R410A units.
LP side
Approx. 2 to 4°C below the tempe-
rature of the leaving chilled water,
for R410A units.
VLS-GB.indd 21 17-06-2009 15:56:45

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir VLH 904 and is the answer not in the manual?

SystemAir VLH 904 Specifications

General IconGeneral
BrandSystemAir
ModelVLH 904
CategoryHeat Pump
LanguageEnglish

Related product manuals