Page 27
English
Control
6.5 HPF version configuration
Units equipped with High pressure fan (HPF) can be
set-up on the field to give the unit a specific static
pressure.
By entering parameter in service level - Max Speed
(Vdc) - it is possible to modify high static pressure.
The table below shows the correspondance between
chiller model, fan RPM, high static pressure.
High Static
Pressure Fan (Pa)
Size
VLS 524
VLS 604
VLS 704
VLS 1004
VLS 1104
VLS 1204
VLS 804
VLS 904
Fan RPM
Parameter in Service
Level: Max Speed (Vdc)
45 900 6,8
70 950 7,3
100* 1000 7,8
130 1050 8,3
160 1100 8,9
50 900 6,8
80 950 7,3
105* 1000 7,8
130 1050 8,3
160 1100 8,9
45 900 6,8
75 950 7,3
100* 1000 7,8
130 1050 8,3
160 1100 8,9
45 900 6,8
75 950 7,3
100* 1000 7,8
130 1050 8,3
160 1100 8,9
50 900 6,8
80 950 7,3
105* 1000 7,8
130 1050 8,3
160 1100 8,9
55 900 6,8
80 950 7,3
105* 1000 7,8
130 1050 8,3
160 1100 8,9
60 900 6,8
85 950 7,3
105* 1000 7,8
130 1050 8,3
160 1100 8,9
60 900 6,8
85 950 7,3
105* 1000 7,8
130 1050 8,3
160 1100 8,9
* Factory configuration in HPF version
VLS-GB.indd 27 17-06-2009 15:56:45