16 RAU-SVX01F-E4
INSTALLATION CHECKLIST
RAUL Trane Air Cooled Condensing Unit
This list must be checked off by the installer to ensure correct installation before the unit starts up.
Unit acceptance
o Check for damage, if any, on transportation
o Check for equipment shipped against delivery slip
o Check lifting system
Unit positioning
o Remove packaging
o Check position of unit
o Check unit is level
o Check clearance around condenser
o Check clearance required for maintenance access
o Check position of rubber pads
Refrigerant circuit
o Check filter dryer and sight glass presence
o Check oil traps presence on discharge line (if there vertical risers>3m)
o Check pitch for horizontal lines (1cm/m)
o Check refrigerant presence
Electrical equipment
o Check direction of rotation of compressors and fan motors
o Check installation and rating of mains power switch/fuse
o Check that electrical connections comply with specification
o Check that electrical connections match information on manufacturer’s identification plate
o Check electrical connections and connections to mains power switch
General
o Check available cooling charge (50% of rated installation load)
o Check with other trades handling installation works
Comments: .......................................................................................................................................................................................
...........................................................................................................................................................................................................
...........................................................................................................................................................................................................
...........................................................................................................................................................................................................
Signature: ............................................................Name .................................................................................................................
Order N° ..........................................................................................................................................................................................
Work site: ........................................................................................................................................................................................
Please return to your local Trane Service Office.