EasyManuals Logo
Home>Trane>Heat Pump>4TWV0048A1000A

Trane 4TWV0048A1000A User Manual

Trane 4TWV0048A1000A
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20
18-BC89D1-1D-EN
Start Up
1. Ensure you have completed the following sections. ”Refrigerant Line Brazing, p. 12 through ”Electrical High Voltage, p. 18
2. Set System Thermostat to OFF.
3. Turn on disconnect(s) to apply power to the indoor and outdoor
units.
ON
OFF
4. Wait 3 hours before starting the unit if the outdoor ambient
temperature is below 85° F.
3 HRS.
5. Run the system using the “Charging Mode-Cooling” test mode
found in the 850/950 comfort control. This is the only approved
method for setting the system charge level by subcooling.
Follow the on-screen prompts.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 4TWV0048A1000A and is the answer not in the manual?

Trane 4TWV0048A1000A Specifications

General IconGeneral
BrandTrane
Model4TWV0048A1000A
CategoryHeat Pump
LanguageEnglish

Related product manuals