Picco R32 Air/water inverter heat pumps with axial fans
45
MENU
MENÙ LABEL PASSWORD LEVEL OTHER CONDITIONS
Setpoint Set User Not accessible if connected to Hi-t2
Probes tP Installer ---
Alarms Err User Only if acve alarms
Digital inputs Id Installer ---
Parameters Par Installer ---
Password PSS User ---
Hours of operaon oHr Installer ---
USB USb Installer
Only with pen drive with relevant
update les
Firmware Version Fir Installer Version, Revision and Sub
Alarm log Hist Installer Only if the log contains data
MENÙ SETPOINT
SETPOINT DESCRIPTION UNIT DEFAULT RANGE
Coo First Summer setpoint °C 7.0 5 ÷ Co2
Hea First Winter setpoint °C 45.0 25 ÷ 60
*San Sanitary setpoint °C 48.0 25 ÷ 60
Coo2 Second Summer setpoint °C 18.0 Coo ÷ 25
Hea2 Second Winter setpoint °C 35.0 25 ÷ Hea
**rCoo Mixing valve summer setpoint °C 15.0 0.0 ÷ 80
**rHEA Mixing valve winter setpoint °C 30.0 0.0 ÷ 80