58
S8V2-SVX001-1A-EN
IFC Component Layout
BAYSENSC360 - Optional Kit for
24V Mode
Table 23. LED's in 24V Mode
Condition
Communication LED Status LED
(Amber) (Green)
Power-Up
Solid ON Solid ON
IDLE ON OFF
Active Demand ON 1 Flash
Active Error ON 2 Flash
Internal Comm Error ON 3 Flash
BLE Pairing ON-Flashing ON-Flashing
Table 24. LED's in Comm Mode
Condition
Communication LED Status LED
(Amber) (Green)
Power-Up
Solid ON Solid ON
IDLE Device Count OFF
Active Demand Device Count 1 Flash
Active Error Device Count 2 Flash
Internal Comm Error Device Count 3 Flash
CAN BUS Error Fast Flash OFF
BLE Pairing ON-Flashing ON-Flashing