RLC-SVU007E-GB
14
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Chilled Water Reset (CWR)
Functional Description
The UC800 shall reset the chilled water temperature setpoint based on return water temperature or outdoor air
temperature. The Return Reset and Outdoor Reset functions are standard.
The chilled water reset settings are as follows:
1. Reset Type – The following options are selectable: No Chilled Water Reset, Outdoor Air Temperature Reset, Return
Water Temperature Reset, or Constant Return Water Temperature Reset.
2. Reset Ratio – For Outdoor Air Temperature Reset, both positive and negative reset ratios will be allowed.
3. Start Reset
4. Maximum Reset – The maximum resets shall be with respect to the chilled water setpoint.
All parameters shall be factory set to a pre determined set of values. Field adjustment of two, three and four above
is expected to be very infrequent. Pre determined factory settings shall be set for all Reset Types.
Variable definitions:
CWS – Arbitrated chilled water setpoint, before any reset has occurred
CWS’ – Active chilled water setpoint, includes the effect of chilled water reset
CWR – Amount of chilled water reset (also called Degrees of Reset).
The above quantities are related by the equation:
CWS’ = CWS + CWR
or
CWR = CWS’ – CWS
With the chiller running and any type of chilled water reset enabled, CWR is allowed to change at a maximum rate of
-17.2°C every 5 minutes until the actual CWR equals the desired CWR. When the chiller is not running, actual CWR
shall be set equal to the desired CWR within one minute (no maximum rate is in effect).
If Chilled Water Reset is disabled, desired CWR is 0.
Additional variable definitions:
RESET RATIO – User adjustable gain
START RESET – User adjustable reference
TOD – Outdoor air temperature
TWE – Evaporator entering water temperature
TWL – Evaporator leaving water temperature
MAXIMUM RESET – User adjustable limit providing the maximum amount of reset.
The equations for each type of reset:
Outdoor Air Temperature Reset
CWR = RESET RATIO * (START RESET – TOD)
With limits:
CWR > 0
CWR < Maximum Reset
Return Water Temperature Reset
CWR = RESET RATIO * (START RESET – (TWE – TWL))
With limits:
CWR > 0
CWR < Maximum Reset
Constant Return Water Temperature Reset
CWR = 100% * (Design Delta Temperature – (TWE – TWL))
With limits:
CWR > 0
CWR < Design Delta Temperature

Other manuals for Trane Tracer TD7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer TD7 and is the answer not in the manual?

Trane Tracer TD7 Specifications

General IconGeneral
BrandTrane
ModelTracer TD7
CategoryController
LanguageEnglish

Related product manuals