right to change design and specifications without notice.
GREEN LED AMBER LED RED LED ERROR
FLASH FLASH FLASH
1 Flame Sensed when no flame should be present
2 Pressure switch stuck closed
3 1st stage pressure switch is open / not closing
4 Open thermal limit or open rollout
5 Open low voltage fuse
6 1st stage pressure switch opened 5 times within one cycle--1 hour lockout
7 System lockout Retry
8 System lockout Recycle
9 Reverse polarity or poor grounding
10 Gas valve energized without call for heat
12 Ignitor relay failure internal in board. Replace IFC
Solid Gas valve relay failure internal in board. Replace IFC
3 Double 2nd stage pressure switch open; system reverts back to 1st stage heat
1 1st stage call for heat
2 2nd stage call for heat
3 W2 call present without W1
4 Y call present without G
Rapid Low flame sense current
1 Standby mode or call for cooling