EasyManuals Logo
Home>Trane>Furnace>TUH1B080A9H31C

Trane TUH1B080A9H31C User Manual

Trane TUH1B080A9H31C
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
18-CD33D1-4 29
Installer’s Guide
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
1 STAGE
HEATING / COOLING
THERMOSTAT FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
OUTDOOR UNIT
(NO TRANSFORMER)
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY
(FIELD SUPPLIED)
SEE NOTE 3
B/C
B/C
B/C
From Dwg. 21B341423 Rev. 2
NOTE:
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C.
Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a
soapy solution before lighting the furnace. DO NOT
CHECK WITH AN OPEN FLAME!
ANSI Z223.1/ NFPA 54 or National Standard of Canada,
Natural Gas and Propane Installation Code, CSA B149.1.
The upflow/ horizontal furnace is shipped standard for
left side installation of gas piping. A knockout is provided
on the right side for an alternate gas piping arrangement.
See Figure 37.
The installation of piping shall be in accordance with pip-
ing codes and the regulations of the local gas company.
Pipe joint compound must be resistant to the chemical re-
action with liquefied petroleum gases.
Refer to piping Table 10, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a manu-
al shut-off valve as shown in Figures 37-39.
National codes require a condensation drip leg to be in-
stalled ahead of the controls as shown in Figures 37-39.
The furnace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of that system at test pressures in ex-
cess of 1/2 psig (3.5 kPa).
The furnace must be isolated from the gas supply piping
by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
GAS PIPING

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TUH1B080A9H31C and is the answer not in the manual?

Trane TUH1B080A9H31C Specifications

General IconGeneral
BrandTrane
ModelTUH1B080A9H31C
CategoryFurnace
LanguageEnglish

Related product manuals