Table 15. Braze the Refrigerant Lines (continued)
4. Wrap a wet rag around the valve body to avoid heat damage and
continue the dry nitrogen purge.
5. Braze the refrigerant lines to the service valves.
a. For Units shipped with a field-installed external drier, check
liquid line filter drier’s directional flow arrow to confirm
correct direction of refrigeration flow (away from outdoor unit
and toward evaporator coil) as illustrated. Braze the filter
drier to the Liquid Line.
6. Continue the dry nitrogen purge. Do not remove the wet rag until
all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen
purge.
Note: Precautions should be taken to avoid heat damage to base pan
during brazing. It is recommended to keep the flame directly
off of the base pan.
3-4” from valve
7. Replace the pressure tap valve cores after the service valves have
cooled.
RReeffrriiggeerraanntt LLiinnee BBrraazziinngg

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Variable Speed ComfortLink II 4TWV8048A1000B and is the answer not in the manual?

Trane Variable Speed ComfortLink II 4TWV8048A1000B Specifications

General IconGeneral
BrandTrane
ModelVariable Speed ComfortLink II 4TWV8048A1000B
CategoryHeat Pump
LanguageEnglish

Related product manuals