Series
Advanced air conditioning systems
H
W
L
2.1 Technical Data Table – WS Package Units (continued)
WS-75 to WS-102 WS-120 and WS-144
Model WS-75 WS-85 WS-102 WS-120 WS-144
Cooling capacity
(1)
Watt 21734 24751 29643 34739 41945
Btu/h 74200 84500 101200 118600 143200
Heating capacity
(1)
Watt 25395 28910 34974 40715 49502
Btu/h 86700 98700 119400 139000 169000
Power
Consumption
(2)
Cooling Watt 5573 6314 7601 8862 10646
Heating Watt 6194 6883 8743 9930 11786
Operating
Current
(2)
Cooling Amp 3x14.9 3x16.2 3x18.2 3x22.4 3x31.1
Heating Amp 3x16.9 3x18.3 3x21.2 3x26.0 3x35
C.O.P
Cooling 3.90 3.92 3.90 3.92 3.94
Heating 4.10 4.20 4.00 4.10 4.20
Air Flow
M
3
/h 4080 4760 5100 6800 8160
CFM 2400 2800 3000 4000 4800
Net Static Pressure
mm H
2
O
6.4 6.4 6.4 7.6 8.9
Water Flow
M
3
/h 3.9 4.5 5.4 6.3 7.6
GPM 17.3 19.6 23.5 27.6 33.2
Heat Rejection-Cooling
Watt 27307 31065 37244 43601 52591
Btu/h 93226 106056 127150 148855 179545
Heat Extraction-Heating
Watt 19201 22027 26231 30785 37716
Btu/h 65554 75201 89551 105099 128763
Power Supply V/Ph/Hz 400/3/50 400/3/50
Time Delay Fuse Amp. 3xC20 3xC25 3xC25 3xC40 3xC40
Water Piping in/out BSP 1¼" 1¼" 1¼" 1½" 1½"
Drain mm 22.2 22.2 22.2 30 30
Refrigerant Charge gr. 3200 3700 3900 4200 6000
Dimensions (LxWxH) mm 1510x700x600 1540x750x610 1650x850x610 2050x1000x630
2050x1100x660
Net Weight Kg. 165 185 195 255 325
1. Design data for cooling: Air entering temperature 27ºC db/19ºC wb and water inlet temperature 29ºC
Design data for heating: Air entering temperature 21ºC and water inlet temperature 20ºC
2. Excluding electrical heating element.
3. Net static pressure available at fan discharge at nominal capacity.
4. Available also in 400/3/50.
Data applicable for R410A. For additional information contact Unique ltd.
Product specifications are subject to change without notice. Appearance of products may differ slightly from catalog.