The set point variable status
Description: The output value and status provided to
an upstream block for output tracking when the loop
is broken or limited, as determined by the status bits.
This information is used to provide bump less
transfer to closed loop control and to prevent windup
under limited conditions when that becomes possible
1: Value
2: Status
Length 1 byte
Write
The set point variable status
Description: Target set point and status provided by a
supervisor Host to a analog control or output block
1: Value
2: Status
Length 1 byte
Read Only
The set point variable status
Description: Block set point and status after ramping
– provided to a supervisory Host for back calculation
and to allow action to be taken under limiting
conditions or made change.
1: Simulate Status
Length 1 byte
Read Write
2: Simulate Value
Length 4 byte
Read Write
3: Current Transducer Status
Length 1 byte
Read Only
4: Current Transducer Value
Length 4 byte
Read Write
5: Simulation Enable/Disable bit
Length 1 byte
Read Write
Description: Allows the transducer analog input or