7 Trouble Guide
7.1 Check “Err Lock Result”
Internally in IHP24 there is a hardware foundation fieldbus module. This module communicates
with the rest of the hardware in IHP24 via a local modbus interface. This interface needs to run at a
fixed setup.
If the “ERR_LOCK_RESULT” parameter is not “Ok” .. but “COMM Err”
On the IHP24 enter the setup menu.
In the Local Display Menu System on the IHP24 go to “Setup Menu”
2. Advanced 6.Modbus 2.Baudrate
Select 38400 baud
2. Advanced 6.Modbus 1.ID
Select 1
2. Advanced 6.Modbus 3.Parity
Select Even
2. Advanced 6.Modbus 4.Stopbits
Select 1
Remember to save when you leave the menu system.