Trouble shooting
Calibrate the analogue output loop 1 from the advanced menu (2.8)
No. 114
Analogue output loop 2 is not calibrated
Description
The analogue output loop 2 is not calibrated
Only applicable when using the proportional regulator
Trouble shooting
Calibrate the analogue output loop 2 from the advanced menu (2.9)
No. 120
Proportional output is not configured
Description
The proportional output signal has not been configured
Only applicable when using the proportional regulator
Trouble shooting
Configure the proportional output signal in the advanced menu (3.1.4)
No. 130
SP has not been set
Description
The SP has not been set through Modbus or Foundation Fieldbus
Only applicable for Modbus or Foundation Fieldbus version
Trouble shooting
Send a SP to the unit.
Contact Val Controls
Consequence
The positioner outputs goes to their fail position.

Other manuals for Val Controls IHP24-BF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IHP24-BF and is the answer not in the manual?

Val Controls IHP24-BF Specifications

General IconGeneral
BrandVal Controls
ModelIHP24-BF
CategoryValve Positioners
LanguageEnglish

Related product manuals