The positioner is not calibrated
Calibrated w. error. Using old values!
The last calibration failed and the positioner is using the parameters from the
previous calibration.
Investigate the Error log to find the reason to why the calibration failed.
The measured travel is not large enough
Increase the travel
Check that the requirements for operating area (3.4 Electrical specifications)
for the position sensor or position loop are used.
No movement or too large actuator
The positioner has not detected any movement
Movement is confirmed visually:
• The actuator is very slow moving. Use manual calibration without auto
tuning
• Check that the position feedback is connected correct
No movement:
• Check that the solenoids are configured correct
• Check the hydraulic system
Travel time too long. Actuator is too big
The travel time is larger than 120 sec
Use manual calibration without auto tuning