TCY3-T0121R
TCY3-T0121R Series Intelligent Compact Controller
Features
• Temperature control for 2-pipe, 4-pipe HVAC
systems.
• -H version: Humidity control with integrated
humidity sensor
• Universal PID and binary control for any
analog input/output signal and range
• 4 independent PID sequences, 12
independent binary sequences
• 1 modulating output for DC 0...10V or 0…20
mA actuators with 10 bit resolution.
• 1 Input for DC 0…5V, 0…10V or 0…20 mA
sensors with 10 bit resolution
• 1 internal temperature sensor and 1 external
sensor input
• Multiple functions on external input: auto
changeover, remote control
• Monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
• Feedback function for internal sensors and
set points.
• Special functions for dehumidifying, set point
shift and VAV control
• Transformation of display value according to
analog sensor range
• Password protected programmable user and
control parameters
• Blue backlight
• Deluxe Version only:
o Power Cap protected real time clock with 24h
power backup
o 16 switching times, grouped in 4 time
schedules.
o Infrared remote control
Applications
• Air Only Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:
o up to two reheat stages
o supply air, extract air cascade control
o humidity control
o Control for variable speed fans
• Air/Water Systems:
o Fan Coil units for 2-pipe or 4-pipe systems with options of:
Humidity control
Pressure control
o radiator control, chilled ceiling
• Water Only Systems: Radiator, floor heating or chilled ceilings
• Individual room control for hotel rooms, meeting rooms, etc.
General Description
The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up
to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2
binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A
detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard
operation terminal. No special tool or software is required.
Doc: 70-000002 V1.0, 20101115 © Vector Controls GmbH, Switzerland Page 1
Subject to alteration