TCI-C-Universal Controller
Doc: 70-00-0123, Date: 20091020 © Vector Controls GmbH Page 1
TCI-C Series cabinet mounted universal controller
Features
• Universal PID and binary control for any analog
input/output signal and range
• 2 independent control loops with each 2 PID sequences and
6 independent binary sequences
• 2 modulating output for DC 0...10V or 0…20 mA actuators
with 10 bit resolution.
• 3 universal inputs for NTC 10k, open contact binary input,
DC 0…10V or 0…20 mA sensors with 10 bit resolution
• 1 PT1000 input -50…200°C (-58…392°F)
• Multiple auxiliary functions: heat – cool auto changeover,
remote control, setpoint compensation
• Cascading of control loops
• Alarm monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
• Feedback function for inputs and set points.
• Special functions for dehumidifying, set point shift and VAV
control
• Password protected programmable user and control
parameters
• Deluxe Version only:
o Power Cap protected real time clock with 24h power
backup
o 8 time schedule events, with many options
o Blue backlight
Applications
• Air Only Systems: Constant or variable air volume systems for single or dual duct systems with options of:
o up to two reheat stages
o supply air, extract air cascade control
o humidity control
o Control for variable speed fans
• Air/Water Systems:
o Fan Coil units for 2-pipe or 4-pipe systems with options of:
Humidity control
Pressure control
o radiator control, chilled ceiling
• Water Only Systems: Radiator, floor heating or chilled ceilings
• Individual room control for hotel rooms, meeting rooms, etc.
General Description
The TCI-C is a stand-alone cabinet mounted electronic universal controller with two autonomous control loops. Each
control loop may use up to 2 PID sequences and 6 binary sequences. The TCI-C11 features 1 independent control loop, 2
universal inputs, 2 binary outputs and one analog output, the TCI-C22 offers 2 independent control loops, 3 universal
inputs, 1 PT1000 input, 2 binary relays outputs and 2 analog outputs. A detailed configuration is possible by following a
simple setup routine. The TCI can be configured using the standard operation terminal. No special tool or software is
required.
Name
Supply Voltage 0 = 24VAC, 1 = 110VAC, 2 = 230VAC
In/Outputs: 1 = 2UI, 2DOR, 1AO, 2 = 1PT1000, 3UI, 2DOR, 2AO
Control loops: 1 = 1 control loop, 2 = 2 control loops
Housing: C = Cabinet, W = Wall mounted
Series:
TCI
T C
I 2
-
C
0
-
2